Thunder 5KW Infini solar VII
SPECIFICATIONS
- Pure sine wave solar inverter
- Self-consumption and Feed-in to the grid
- Programmable supply priority for PV, Battery or Grid
- User-adjustable charging current and voltage
- Programmable multiple operation modes: Grid-tie, off-grid and grid-tie with backup
- Monitoring software for real-time status display and control
- Parallel operation up to 9 units
- Battery Independent system


MODEL | THUNDER V2 INFINI |
---|---|
Max. PV Array Power | 5000 W |
Rated Output Power | 5000 W |
Maximum PV Array Open Circuit Voltage | 450 VDC |
MPPT Range @ Operating Voltage | 120 VDC ~ 430 VDC |
MPP Tracker Number | 1 |
GRID-TIE OPERATION | |
GRID OUTPUT (AC) | |
Nominal Output Voltage | 220 / 230 / 240 VDC |
Output Voltage Range | 184 – 264.5 VAC or 195.5 – 253 VAC (Selectable) |
Nominal Output Current | 21.7 A |
Power Factor | > 0.99 |
EFFICIENCY | |
Maximum Conversion Efficiency (DC/AC) | 95 % |
OFF-GRID, HYBRID OPERATION | |
GRID INPUT | |
Acceptable Input Voltage Range | 90 – 280 VAC or 170 – 280 VAC |
Frequency Range | 50 Hz / 60 Hz (Auto sensing) |
Maximum AC Input Current | 40 A |
BATTERY MODE OUTPUT (AC) | |
Nominal Output Voltage | 220 / 230 / 240 VAC |
Output Waveform | Pure sine wave |
Efficiency (DC/AC) | 93 % |
BATTERY & CHARGER | |
Nominal DC Voltage | 40 VDC |
Maximum Solar Charge Current | 80 A |
Maximum AC Charge Current | 80 A |
Maximum Charge Current | 80 A |
GENERAL | |
PHYSICAL | |
Dimension, D x W x H (mm) | 120 x 295 x 468 |
Net Weight (kgs) | 12 |
INTERFACE | |
Parallel Function | Yes, 9 units |
Communication Ports | USB, RS-232 and dry contact |
ENVIRONMENT | |
Humidity | 0 to 90% RH (Non-condensing) |
Operating Temperature | -10°C to 50°C |